INSPECTION DETAILS FOR PERMIT 21120481
Permit Number 21120481 Owner Name PIOCNACIA RACHEL + JAMESON G
Permit Type SOLAR Permit Address 3829 RAMIRO ST
Inspection Type FINAL-1 City/State/Zip SEBRING, FL 33872
Inspect Area AP Inspector CHUCK
Request Date 03-23-2022 Scheduled Date 03-24-2022
Instructions  
Contact Info  
Contractor   Inspect Date 03-24-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7315489
Fee ID BRI
Inspector Notes
Date Text
2022-03-24 15:04:50.00000REMOVE NEUTRAL BONDING SCREW IN EXTERIOR PV DISCONNECT;
 BOND ENCLOSURE WITH EQUIPMENT GROUNDING CONDUCTOR ONLY.