-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 21110213
Permit Number 21110213 Owner Name MUNOZ RUFINO + FIDELIA
Permit Type SOLAR Permit Address 2319 CROYDON RD
Inspection Type FINAL-1 City/State/Zip SEBRING, FL 33870
Inspect Area   Inspector CHUCK
Request Date 01-07-2022 Scheduled Date 01-10-2022
Instructions  
Contact Info MARINES R 4074562743
Contractor   Inspect Date 01-10-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7310862
Fee ID BRI
Inspector Notes
Date Text
2022-01-10 14:59:10.000001] ADD GROUND BAR IN COMBINER PANEL, SEPARATE
 GROUNDS/NEUTRALS
 2] BOND NEUTRAL IN PV DISCONNECT
 3] INSTALL RACEWAY FOR SUPPLY-SIDE CONDUCTORS THROUGH
 BLOCK WALL; OPEN CONDUCTORS NOT APPROVED
 4] FILL IN AC CURRENT/VOLTAGE LABEL
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved