-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 21110151
Permit Number 21110151 Owner Name WILLIAMS KARL FITZGERALD JR
Permit Type SOLAR Permit Address 201 LOON AVE
Inspection Type FINAL-1 City/State/Zip SEBRING, FL 33870-
Inspect Area SE Inspector CHUCK
Request Date 01-04-2022 Scheduled Date 01-05-2022
Instructions  
Contact Info  
Contractor   Inspect Date 01-05-2022
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7310620
Fee ID BRI
Inspector Notes
Date Text
2022-01-05 15:08:52.000001] FAILURE TO CALL FOR UNDERGROUND CONDUIT INSPECTION.
 PROVIDE VERIFICATION OF MINIMUM COVER OF UNDERGROUND
 CONDUIT. SEE REVIEWER COMMENT ON SHEET PV-2A.
 2] INSTALL GROUNDING ELECTRODE SYSTEM CONNECTED TO PV
 SYSTEM FRAME AT REMOTE BUILDING. SEE 690.47 AND
 REVIEWER COMMENT ON SHEET PV-2A.
 3] INSTALL RAPID SHUTDOWN GRAPHIC LABEL. SEE 690.56 C 1
 AND SHEET PV-7.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved