-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 21110149
Permit Number 21110149 Owner Name HARRIS KRISTINE M
Permit Type SOLAR Permit Address 7009 PARKWOOD ST
Inspection Type FINAL-1 City/State/Zip SEBRING, FL 33876
Inspect Area SE Inspector CHUCK
Request Date 12-22-2021 Scheduled Date 12-27-2021
Instructions  
Contact Info MARINES R 4074562743
Contractor   Inspect Date 12-27-2021
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7310179
Fee ID BRI
Inspector Notes
Date Text
2021-12-27 14:19:09.000001] APPROVED MARKED-UP PLANS MUST BE ON JOBSITE
 2] ONE-LINE DIAGRAM MISSING FROM PLANS LEFT ON JOBSITE
 (NOT MARKED-UP SET)
 3] CONDUCTORS BETWEEN SERVICE TAP AND COMBINER ARE
 UNDERSIZED FOR SYSTEM (ASSUMING CORRECT AC CURRENT
 LABEL). 52.28 X 1.25 = 66. MAXIMUM 75 DEGREE AMPACITY
 OF INSTALLED #6 IS 65 AMPS PER 310.15 B 16; SEE ALSO
 110.14.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved