-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Inspection Details
INSPECTION DETAILS FOR PERMIT 21061018
Permit Number 21061018 Owner Name SMITH MELVIN + DOLORES
Permit Type SOLAR Permit Address 5823 COLUMBUS BLVD
Inspection Type FINAL-1 City/State/Zip SEBRING, FL 33872
Inspect Area   Inspector CHUCK
Request Date 08-26-2021 Scheduled Date 08-31-2021
Instructions  
Contact Info  
Contractor   Inspect Date 08-31-2021
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7303753
Fee ID BRI
Inspector Notes
Date Text
2021-08-31 12:49:52.000001] NO APPROVED PLANS OR PERMIT CARD ON SITE
 2] AC VOLTAGE/CURRENT LABEL NOT COMPLETED
 3] SYSTEM USES 47 MODULES; IF IQ7+ INVERTERS (@1.21
 AMPS), THEN 70 AMP FUSES ARE UNDERSIZED. VERIFY BY
 APPROVED DRAWINGS.
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved