INSPECTION DETAILS FOR PERMIT 20080327
Permit Number 20080327 Owner Name KNIGHTEN REGINALD + FELITA
Permit Type SOLAR Permit Address 44 A MIRACLE AVE
Inspection Type FINAL-1 City/State/Zip AVON PARK, FL 33825
Inspect Area AP Inspector CHUCK
Request Date 09-24-2020 Scheduled Date 09-25-2020
Instructions  
Contact Info  
Contractor   Inspect Date 09-25-2020
Result F Fail Code  
Comments  
Work Time   Confirmation Number 7287263
Fee ID BRI
Inspector Notes
Date Text
2020-09-25 15:04:16.00000REMOVE GROUNDED CONDUCTOR (NEUTRAL) BONDING IN PV
 COMBINER PANEL. GROUNDS AND NEUTRAL MUST BE
 ELECTRICALLY SEPARATED; ENSURE THAT ENCLOSURE IS BONDED
 TO GREEN CONDUCTOR ONLY.
 PROVIDE PERMIT CARD ON SITE.