INSPECTION DETAILS FOR PERMIT 19020494
Permit Number 19020494 Owner Name YOUMANS SHERMAN O TR
Permit Type BRNFRSTEEL Permit Address 3 MIA CASA LN
Inspection Type ELECTRICAL-1 City/State/Zip LAKE PLACID, FL 33852
Inspect Area LP Inspector CHUCK
Request Date 10-23-2019 Scheduled Date 10-24-2019
Instructions  
Contact Info  
Contractor HC00765 Inspect Date 10-23-2019
Result I Fail Code  
Comments SEE ELEC NOTES
Work Time   Confirmation Number 7274730
Fee ID  
Inspector Notes
Date Text
2019-10-23 15:15:09.000001] CHANGE AC BRKR TO 25A
 2] CHANGE AIR HANDLER BRKR TO 30A
 3] CONNECT #6 BOND CONDUCTOR IN BACK OF BLDG ADJACENT
 TO AC UNIT
 4] CONNECT POWER TO WATER HEATER
 5] ADJUST/REWORK PANEL DEADFRONT; MUST FIT CLOSELY
 AROUND CIRCUIT BREAKERS WITHOUT GAPS.