Case Description
UNSAFE ELECTRIC-ONE BREAKER BOX FOR FOUR (4) POST,
PUMP, LIFTSTATION AND SIX (6) POST W/FAULTY
ELECTRIC WITH EXPOSED WIRES, SOME WIRES HAVE
CAUGHT FIRE AND ARE BURN. THERE ARE WIRES ABOVE
GROUND WITHOUT CONDUIT RUNNING FROM ONE MOBILE
HOME TO THE OTHER. NEED NEW BREAKER BOX INSTALLED.
CONTACT RAYMOND @ 863-303-7671.
Inspections/Events Detail
DATETIMEINSPECTION / EVENT TYPEINSTRUCTIONS / COMMENTS
05-03-202107:28 PMCLOSE COMPLAINTCASE CLOSED BY ELONGSHO
05-03-202107:28 PMREINSPECTIONPROPERTY IS IN COMPLIANCE. CLOSE CASE.
05-06-201905:22 PMREINSPECTIONRECEIVED CALL FROM SANDRA TYRELL
(655-2252) TO EXPLAIN THAT COMPLAINTANT
HAS BEEN SQUATTING ON PROPERTY AND IS IN
PROCESS OF BEING EVICTED. SHE WILL HAVE
LICENSED ELECTRICIAN OBTAIN PERMIT FOR
REPAIRS WHEN SQUATTERS ARE REMOVED FROM
PROPERTY.
04-29-201904:22 PMINITIAL INSPECTIONMADE SITE VISIT AND MET WITH RAYMOND.
FOUND THE FOLLOWING ELECTRICAL CONCERNS.
1] SERVICE POLE LEANING; UTILITY DROP
LOWER THAN REQUIRED MINIMUM CLEARANCE
FROM GRADE. POLE HAS DETERIORATED AT
GROUND LEVEL.
2] AT THE SERVICE POLE, A 100 AMP
BREAKER IS SUPPLYING POWER TO A 10/2
TYPE UF CABLE. IF USED, THIS CABLE MUST
HAVE OVERCURRENT PROTECTION NOT
EXCEEDING 30 AMPS. HOWEVER, THE CABLE IS
UNDERSIZED FOR THE LOADS IT IS CONNECTED
TO (AT LEAST 3 RV OUTLETS).
3] CABLE REFERENCED IN ITEM #2 IS LYING
ON THE GROUND SURFACE AND IS SUBJECT TO
CONTACT AND DAMAGE. OBSERVED AT LEAST
ONE SPLICE COVERED WITH DUCT TAPE.
4] CABLE REFERENCED IN ITEM #2 IS
SUPPLYING 120/240 VOLTS TO A REMOTE LOAD
CENTER. AS SUCH, IT IS USING THE BARE
EQUIPMENT GROUNDING CONDUCTOR AS A
COMMON NEUTRAL, AND IS LACKING A
SEPARATE EQUIPMENT GROUND CONDUCTOR.
5] ALL OTHER FEEDERS/BRANCH CIRCUITS
HAVE BEEN DISCONNECT FROM THE SERVICE
PANEL. PANEL BUSS IS SEVERELY CORRODED.
THESE ELECTRICAL ISSUES CONSTITUTE A
HAZARDOUS CONDITION AND MUST BE
CORRECTED BY A LICENSED ELECTRICAL
CONTRACTOR. PERMIT WILL BE REQUIRED AND
INSPECTION MADE. I WILL SEND A COPY OF
THIS REPORT TO OWNER FOR THEIR
COMPLIANCE. FAILURE TO OBTAIN PERMIT AND
CORRECT HAZARDOUS CONDITIONS WILL RESULT
IN CODE ENFORCEMENT PROCESS AND
PROCEDURES.
04-25-201902:55 PMCREATE COMPLAINTCOMPLAINT RECORDED BY NSULLIVA