Code Enforcement Detail
Code Enforcement Detail
Case Number CE18040158 complainant  
Case Date 04-30-2018 address  
Origination   -   Status C - CLOSED
Operator nsulliva Officer ERIC
Fines Balance $0.00
Lien Balance $0.00
Total Balance $0.00
Property On Case
STRAP NBR C-30-36-30-010-0060-0140 Owner SPICER STEPHEN + PENNY
Unit   Owner Address 1314 LAKE CLAY DR
Property Address 1314 LAKE CLAY DR City/State/Zip LAKE PLACID FL 33852
City/State/Zip LAKE PLACID FL 33852 Phone  
Case Description
OWNER REQUEST HOME INSPECTION AFTER STORM
STEVE SPICER@ 863-464-1744
Inspections/Events Detail
DATETIMEINSPECTION / EVENT TYPEINSTRUCTIONS / COMMENTS
11-19-201809:15 AMCLOSE COMPLAINTCASE CLOSED BY CSHACKEL
11-19-201809:15 AMREINSPECTIONHOUSE AND ADDITIONS HAVE BEEN DEMOED AND
REMOVED.
05-01-201806:06 PMINITIAL INSPECTIONMET WITH OWNER AND GREG FROM G&N
DEVELOPMENT. THIS HOME HAS SUFFERED
HURRICANE DAMAGE. THE REAR SCREEN PATIO
IS COMPLETELY REMOVED. THE CONCRETE SLAB
THAT THIS ROOM WAS ATTACHED TO SHOWS
SIGNIFICANT SETTLING WITH MAJOR CRACKS
IN THE SLAB. THIS WOULD INDICATE THAT
THERE ARE NO FOOTERS BENEATH THIS SLAB.
FOOTERS WILL BE REQUIRED FOR REPLACEMENT
OF THIS SCREEN STRUCTURE. THERE IS ALSO
AN ADDITION ON THE EAST (LAKE) SIDE OF
THE HOME. THE EXTERIOR WALLS OF THIS
ADDITION ARE PARTIALLY CBS AND PARTIALLY
WOOD FRAME CONSTRUCTION. THE WOOD FRAME
WALL DOES NOT MEET BUILDING CODE
REGULATIONS AND SHOWS SIGNS THAT IT HAS
SUFFERED WIND DAMAGE. AT THE CONNECTION
OF THE CBS AND WOOD FRAME WALL THE CMU
BLOCK BOND BEAM HAS BROKEN LOOSE. THIS
WOULD INDICATE THAT THE WALL HAS MOVED,
POSSIBLY LIFTED, SIGNIFICANTLY TO BREAK
THIS BOND. THE CONCRETE FLOOR OF THIS
ADDITION ALSO SHOWS SIGNS OF SETTLEMENT
WHICH CAUSES QUESTION OF FOUNDATIONAL
FOOTING IN THIS AREA. THE INTERIOR WALL
OF THIS ADDITION IS ALSO NOT CODE
COMPLIANT. WHEN ADDITION WAS ADDED A
PORTION OF THE REAR CMU WALL OF THE MAIN
STRUCTURE WAS REMOVED LEAVING THE CMU
HEADER AND BOND BEAM WITH NO SUPPORT. A
6X6 WOOD POST WAS INSTALLED TO SUPPORT
THIS CMU HEADER AND BEAM WHICH DOES NOT
MEET CODE REQUIREMENTS, CURRENT OR AT
TIME OF CONSTRUCTION. THERE IS ALSO A
WOOD SUPPORT BEAM INSTALLED ACROSS THE
REST OF THIS WALL OPENING THAT SUFFERS
THE SAME NONCOMPLIANT ISSUES. THIS REAR
SECTION OF THE EXISTING STRUCTURES WALL
WILL HAVE TO BE REMOVED AND REPLACED
WITH COMPLIANT CONSTRUCTION ENGINEERED
FROM FOUNDATION THROUGH ENTIRE LOAD
PATH. I RECOMMENDED THAT INVESTIGATION
BE DONE TO INSPECT THE FOUNDATION SYSTEM
BENEATH THE ADDITIONS EXTERIOR WALLS AND
AN ENGINEERS DETERMINATION OF
SUITABILITY OF FUTURE USE.
04-30-201808:47 AMCREATE COMPLAINTCOMPLAINT RECORDED BY NSULLIVA